ASHRAE 90.1-2001 Section: 9.2.1.2 - Space Control |
||||
|
Toolbox |
Requirements: Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall
Exceptions: Remote location shall be permitted for reasons of safety or security when the remote control device has an indicator pilot light as part of or next to the control device and the light is clearly labeled to identify the controlled lighting.
|
||||
|
|||||
|
|||||