HOME          LEED          ASHRAE          EPAct 2005         RESIDENTIAL         CONTROLS          FIND A SALES AGENT

ASHRAE 90.1-2004

Section: 9.4.2 - Tandem Wiring

Toolbox

Requirements:

Luminaires designed for use with one or three linear fluorescent lamps greater than 30 watts each shall use two-lamp tandem-wired ballasts in place of single-lamp ballasts when two or more luminaires are in the same space and on the same control device.

Exceptions:

  1. Recessed luminaires more than 10 ft apart measured center to center.
  2. Surface-mounted or pendant luminaires that are not continuous.
  3. Luminaires using single-lamp high-frequency electronic ballasts.
  4. Luminaires using three-lamp high-frequency electronic or three-lamp electromagnetic ballasts.
  5. Luminaires on emergency circuits.
  6. Luminaires with no available pair.
     

 

ASHRAE Home Site

 

 

 

 

 ã Acuity Brands Lighting, Inc.     Comments   |  Site Terms