Requirements:
Luminaire
wattage incorporated into the installed interior lighting power shall be
determined in accordance with the following criteria:
New in 2007
-
The wattage of incandescent or tungsten-halogen
luminaires with medium screw base sockets and not containing
permanently installed ballasts shall be the maximum labeled wattage
of the luminaire.
-
The wattage of luminaires with permanently
installed or remote ballasts or transformers shall be the
operating input wattage of the maximum lamp/auxiliary combination
based on values from the auxiliary manufacturers’ literature
or recognized testing
laboratories or shall be the maximum labeled wattage of the
luminaire.
-
For line-voltage lighting track and plug-in
busway, designed to allow the addition and/or relocation of
luminaires without altering the wiring of the system, the wattage
shall be
-
the specified wattage of the luminaires included
in the system with a minimum of 30 W/linear ft or
-
the wattage limit of the system’s circuit breaker
or
-
the wattage limit of other permanent
current-limiting device(s) on the system.
-
The wattage of low-voltage lighting track, cable
conductor, rail conductor, and other flexible lighting systems that
allow the addition and/or relocation of luminaires without altering
the wiring of the system shall be the specified wattage of the
transformer supplying the system.
-
The wattage of all other miscellaneous lighting
equipment shall be the specified wattage of the lighting equipment.
Exceptions:
None. |